ZTCJ / Technical file · Design guide / Construction

Solid conductor vs strand

Copper-clad steel stranded conductor
0.6 / 0.8 / 1.0 mmCopper layer · 0.25 mm plated also supplied
15–40 % IACSConductivity
DL/T 1312-2023Product standard
IEEE 80-2013Sizing basis
← Back to the guide index

Construction: solid conductor vs strand

Copper-clad steel selection guide, part 3 of 8

Rule: where a solid conductor (round or flat) will do, do not use strand. For the buried electrode, solid first; for the bonding conductor between electrode and equipment – mostly at or near the surface – strand may be used where it helps. Based on ASTM B227-04, DL/T 1312-2023, DL/T 2727-2023 and project experience.

Solid conductor – first choice

  • Better corrosion resistance. At equal cross-section and copper content, strand has a thinner copper layer, and the more wires the thinner it gets; solid has the thickest.
  • Lower cost. Formed in one pass; strand needs single wires first, then stranding and straightening.
  • Verifiable quality. Copper thickness is the decisive quality parameter. On solid conductor a hand-held coating gauge measures it on site; on strand it cannot be measured once stranded, and the single wires are below the range of ordinary gauges.

Strand – where it helps

  • Its advantage is flexibility. Far more flexible than solid at the same cross-section – tight spaces between equipment and electrode, awkward corners.
  • For bonding conductors, not for the buried electrode. Acceptable where corrosion demands are moderate.
  • Specify the minimum copper thickness per wire. On strand marked "≥ 0.25 mm" the actual thickness follows from conductivity grade and wire diameter; 0.25 is only the floor.

At equal total section and copper fraction, dividing into more wires of equal diameter reduces the absolute copper thickness per wire; fixing the per-wire thickness instead gives a different comparison. The number of wires alone does not set the life – the minimum copper thickness per wire does. This is why our IEEE P80 contribution asks that strand be specified by number of wires, wire diameter and per-wire minimum copper thickness.

← Back to the guide index

Have a project in mind?

Send the conductor size, length, soil and fault current – two sizing options and the copper saving come back within 24–48 hours, free.

Request the free assessmentJust a quotation