ZTCJ / Technical file · Design guide / Process

Electroplated, continuous-cast, pressure-bonded

Copper-clad steel product cross-sections
0.6 / 0.8 / 1.0 mmCopper layer · 0.25 mm plated also supplied
15–40 % IACSConductivity
DL/T 1312-2023Product standard
IEEE 80-2013Sizing basis
← Back to the guide index

Process: electroplated, continuous-cast, pressure-bonded

Copper-clad steel selection guide, part 2 of 8

The three primary bonding processes map onto the three classes in the family definition: electrodeposition, cast bonding and pressure bonding. They determine how thick the copper can be, whether the conductor can be annealed, and where each is the economic choice.

ProcessElectroplated (electrodeposition)Continuous-cast (cast bonding)Pressure-bonded, incl. hot-roll bonding
PrincipleCopper electrodeposited onto the steel core in an electrolyteSteel core passes through molten copper; copper crystallises onto it – metallurgical bond, no interface gapCopper strip or tube bonded to the steel core under heat and pressure, then rolled and drawn
Copper thickness< 0.3 mm, typically 0.25 mm0.25 – 1.0 mm, produced to the design thicknessSet by conductivity grade (30% / 40% IACS; ASTM B910 requires copper ≥ 5% of the diameter)
TemperUsually supplied hard; whether it can be annealed depends on the bond of the plating – as declared by the supplierCan be fully annealed to a soft temper for bending and layingStrand normally hard-drawn
EconomicsCheaper below 0.3 mm copperCheaper above 0.3 mm copperSuited to strand and volume production to a conductivity grade
Typical productsVertical ground rods (UL 467 / IEC 62561-2 convention)Horizontal round wire and tape, thick-layer rods, strand30% / 40% IACS strand (North American telecom and utility bonding conductor)
Standards directionBoth Chinese CCS standards recommend it for vertical electrodes; historically the larger volumeBoth Chinese CCS standards recommend it for horizontal and vertical electrodes; the direction of travelThe construction behind the CCS wire constants in IEEE 80 Table 1
Decision rule: vertical rod, low-corrosion soil, 0.25 mm copper sufficient → electroplated is the economic choice. Horizontal conductor, medium or high-corrosion soil, copper ≥ 0.6 mm, or soft temper needed for laying → continuous-cast. Flexible bonding conductor bought to a conductivity grade → pressure-bonded or continuous-cast strand. We do not recommend electroplated CCS above 0.3 mm copper: the cost advantage disappears and the hard temper makes installation harder.

DL/T 1312-2023 clause 4.2: "copper-clad steel should be produced by continuous casting or electroplating; the sleeve cold-drawing process shall not be used; horizontal electrodes should be annealed." Q/GDW 10466-2021 makes the same recommendation on temper. Electroplated CCS on the market is mostly hard rod stock, though 0.25 mm-class plated round conductor for horizontal laying also exists (North American copper-bonded round conductor, for example); the combined requirement for an annealed temper and a thick layer is what points to continuous casting – a direction on process, not a verdict on electroplating. Sleeve cold-drawing (a steel core drawn inside a copper tube) has no bond at the copper–steel interface and was explicitly prohibited for power earthing by the 2023 revision.

Product designation per DL/T 1312-2023 clause 5: CCS – process code (EP electroplated / CC continuous-cast) – conductivity grade – minimum copper thickness – size. Example: CCS CC 25-0.8-Ø16 is a continuous-cast round wire, 25% IACS grade, 0.8 mm minimum copper, Ø16; CCS CC 20-0.6-50×5 a 50×5 continuous-cast tape.

← Back to the guide index